Modelling and simulation of air-conditioning cycles

Autor: Kazuya Minakuchi, Hisae Takeuchi, Tatsuya Hasegawa, Katsunori Murayama, Yoshinori Kadono, Sandi Rais
Rok vydání: 2016
Předmět:
Zdroj: Heat and Mass Transfer. 53:425-438
ISSN: 1432-1181
0947-7411
Popis: The heat-pump cycle for air conditioning was investigated both numerically and experimentally by evaluating the coefficient of performance (COP) under Japanese Industrial Standard (JIS B 8619:1999) and ANSI/AHRI standard 750-2007 operating conditions. We used two expansion valve coefficients $$Cv_{(\varphi )} = 0.12$$ for standard operating conditions (Case 1) approaching 1.3 MPa at high pressure and 0.2 MPa at low pressure, and $$Cv_{(\varphi )} = 0.06$$ namely poor operating conditions (Case 2). To improve the performance of the air conditioner, we compared the performance for two outside air temperatures, 35 and 40 °C (Case 3). The simulation and experiment comparison resulted the decreasing of the COP for standard operating condition is equal to 14 %, from 3.47 to 2.95 and a decrease of the cooling capacity is equal to 18 %, from 309.72 to 253.53 W. This result was also occurred in poor operating condition which the COP was superior at 35 °C temperature.
Databáze: OpenAIRE