Autor: |
Hwang Yong Jeon, Dong Soo Song, Sang Jun Ha, Je Joong Seong, Seong Cheol Huh |
Rok vydání: |
2014 |
Předmět: |
|
Zdroj: |
Journal of Energy Engineering. 23:186-190 |
ISSN: |
1598-7981 |
DOI: |
10.5855/energy.2014.23.3.186 |
Popis: |
Nuclear Power Plants require the control ability of chemical condition (pH) because pH control during transient accident such as LOCA makes an able the fission product removal capability to be maintained, stress corrosion cracking of stainless steel equipment to be prevented and the production of hydrogen by aluminum and zinc to be minimized. An NPP is designed to control the pH of containment spray and sump coolant using the spray additives 30% NaOH in the event of loss of coolant accident. In this paper, the pH of sump coolant of an NPP during LOCA was analyzed and the fission products removal constant and decontamination factor were calculated according to Standard Review Plan 6.5.2 related to spray chemical conditions of pH. The calculated pH value of recirculation mode using the computer code corresponds to 8.09 9.67, which meets the chemical environment regulation requirements. The fission product removal capability caused by containment spray system is performed to provide input to radiation analysis. |
Databáze: |
OpenAIRE |
Externí odkaz: |
|