Analysis of a damaged industrial hall subjected to the effects of fire
Autor: | Michal Tomko, Sergej Priganc, Ivo Demjan, Stanislav Kmet, Ladislav Pesek |
---|---|
Rok vydání: | 2016 |
Předmět: |
Engineering
business.industry Mechanical Engineering Thermal power station Truss Geodetic datum 020101 civil engineering 02 engineering and technology Building and Construction Structural engineering Static analysis Finite element method Load bearing 0201 civil engineering 020303 mechanical engineering & transports 0203 mechanical engineering Mechanics of Materials Fire resistance business Reliability (statistics) Civil and Structural Engineering |
Zdroj: | Structural Engineering and Mechanics. 58:757-781 |
ISSN: | 1225-4568 |
Popis: | The results of diagnostics and analysis of an industrial hall located on the premises of a thermal power plant severely damaged by fire are presented in the paper. The comprehensive failure-related diagnostics, non-destructive and destructive tests of steel and concrete materials, geodetic surveying of selected structural members, numerical modelling, static analysis and reliability assessment were focused on two basic goals: The determination of the current technical condition of the load bearing structure and the assessment of its post fire resistance as well as assessing the degree of damage and subsequent design of reconstruction measures and arrangements which would enable the safe and reliable use of the building. The current mechanical properties of the steel material obtained from the tests and measured geometric characteristics of the structural members with imperfections were employed in finite element models to study the post-fire behaviour of the structure. In order to compare the behaviour of the numerically modelled steel roof truss, subjected to the effects of fire, with the real post-fire response of the damaged structure theoretically obtained resistance, critical temperature and the time at which the structure no longer meets the required reliability criteria under its given loading are compared with real values. A very good agreement between the simulated results and real characteristics of the structure after the fire was observed. |
Databáze: | OpenAIRE |
Externí odkaz: |