Analysis of Single Phase-to-Ground Fault in Mixed Neutral Ground Systems Using Wavelet Transform
Autor: | D. S. Osipov, B. Yu. Kisselyov, D. S. Satpaev |
---|---|
Rok vydání: | 2018 |
Předmět: |
Computer science
020209 energy Bandwidth (signal processing) Wavelet transform 02 engineering and technology Fault (power engineering) Symmetrical components Electric power system symbols.namesake Fourier transform Wavelet 0202 electrical engineering electronic engineering information engineering symbols Algorithm Continuous wavelet transform |
Zdroj: | 2018 International Conference on Industrial Engineering, Applications and Manufacturing (ICIEAM). |
DOI: | 10.1109/icieam.2018.8728788 |
Popis: | Most faults in distribution networks are single phase-to-ground faults. The paper presents the analysis procedure of single phase-to-ground fault in mixed neutral ground systems. The procedure is based on a wavelet transform applied to the signal of zero sequence current. The wavelet transform is specific in application compared to a widely used short-time Fourier transform in terms of no need for bandwidth selection. The application of wavelet transform in the method proposed in the paper for defining signal energy allows one to avoid drawbacks of the Fourier transform and give more accurate data on signal energy for different ranges. This in its turn allows the charge and discharge frequencies to be extracted more precisely. In addition, this method allows identifying the line of a single phase-to-ground fault. |