Autor: |
Alan S. Fung, Getu Hailu, Peter Dash |
Rok vydání: |
2014 |
Předmět: |
|
Zdroj: |
Volume 2: Economic, Environmental, and Policy Aspects of Alternate Energy; Fuels and Infrastructure, Biofuels and Energy Storage; High Performance Buildings; Solar Buildings, Including Solar Climate Control/Heating/Cooling; Sustainable Cities and Communities, Including Transportation; Thermofluid Analysis of Energy Systems, Including Exergy and Thermoeconomics. |
DOI: |
10.1115/es2014-6455 |
Popis: |
A theoretical investigation of a variable capacity air-to-air air source heat pump (VC-ASHP) coupled with a building integrated photovoltaic/thermal (BIPV/T) system is presented in this paper. The BIPV/T system was integrated into the roof and the wall. Air was circulated behind the photovoltaic arrays to recover the thermal energy. The warm air recovered was supplied to the VC-ASHP. The thermal performance of the VC-ASHP was investigated for three scenarios when the heat pump is running in heating mode. The three scenarios are: (A) by feeding the ambient air to the ASHP; (B) by coupling the ASHP to the wall integrated BIPV/T only; and (C) by coupling the ASHP to the roof integrated BIPV/T only. The coefficient of performance (COP) of the VC-ASHP was evaluated for these three separate scenarios and compared. A typical winter day result suggests that the COP of the ASHP can be improved by coupling the VC-ASHP to either of the BIPV/T systems, i.e., either to the roof integrated BIPV/T system or to the wall integrated BIPV/T system.Copyright © 2014 by ASME |
Databáze: |
OpenAIRE |
Externí odkaz: |
|