Performance of Underfloor Air Distribution in a Field Setting
Autor: | Man Pun Wan, Christopher Y.H. Chao, Douglas P. Sullivan, William J. Fisk, L. Zagreus, Tom Webster, David Faulkner |
---|---|
Rok vydání: | 2006 |
Předmět: |
Pollutant
Engineering business.industry Environmental engineering Building and Construction Thermal stratification Satisfaction rating Energy requirement Indoor air quality Control and Systems Engineering Thermal Electrical and Electronic Engineering business Air quality index Underfloor air distribution Civil and Structural Engineering |
Zdroj: | International Journal of Ventilation. 5:291-300 |
ISSN: | 2044-4044 1473-3315 |
DOI: | 10.1080/14733315.2006.11683746 |
Popis: | Underfloor air distribution (UFAD) is a new method of supplying heated or cooled air throughout a building. Reported advantages of UFAD include energy savings and improved indoor air quality (IAQ). We measured several aspects of the performance of an UFAD system installed in a medium-size office building. The measured air change effectiveness was very close to unity, which is comparable to that measured in buildings with typical overhead air distribution. The pollutant removal efficiency for carbon dioxide was 13% higher than expected in a space with well-mixed air, suggesting a 13% reduction in exposures to occupant generated pollutants. The increase in indoor air temperatures with height above the floor was only 1 to 2 C. This amount of thermal stratification could reduce the sensible energy requirements for cooling of outdoor air by approximately 10%. The occupant's level of satisfaction with thermal conditions was well above average and this high satisfaction rating could possibly be due, in all or part, to the use of a UFAD system. The results of this study provide some evidence of moderate energy and IAQ-related benefits of UFAD. Before general conclusions are drawn, the benefits need to be confirmed in other studies. |
Databáze: | OpenAIRE |
Externí odkaz: |