Performance of thermal distribution systems in large commercial buildings
Autor: | Tengfang T. Xu, Duo Wang, Jennifer A. McWilliams, Francois Remy Carrie, William J. Fisk, Mark P. Modera, Darryl Dickerhoff |
---|---|
Rok vydání: | 2002 |
Předmět: |
Engineering
business.industry Mechanical Engineering Airflow Electrical engineering Variable air volume Building and Construction Mechanics Thermal conduction Thermal ASHRAE 90.1 Duct (flow) Constant air volume Electrical and Electronic Engineering business Civil and Structural Engineering Leakage (electronics) |
Zdroj: | Energy and Buildings. 34:215-226 |
ISSN: | 0378-7788 |
DOI: | 10.1016/s0378-7788(01)00112-8 |
Popis: | This paper presents major findings of a field study on the performance of five thermal distribution systems in four large commercial buildings. The five systems studied are typical single-duct or dual-duct constant air volume (CAV) systems and variable air volume (VAV) systems, each of which serves an office building or a retail building with floor area over 2000 m 2 . The air leakage from ducts is reported in terms of effective leakage area (ELA) at 25 Pa reference pressure, the ASHRAE-defined duct leakage class C L , and air leakage ratios. The specific ELAs ranged from 0.7 to 12.9 cm 2 /m 2 of duct surface area, and from 0.1 to 7.7 cm 2 /m 2 of floor area served. The ASHRAE-defined duct leakage classes ranged from 34 to 606 for the five systems and systems sections tested. The air leakage ratios were estimated to be up to approximately one-third of the fan-supplied airflow in the constant air volume systems. The specific ELAs and leakage classes indicated that air leakage in large commercial duct systems varied significantly from system to system, and from system section to system section even within the same thermal distribution system. Overall, the duct systems measured were much leakier than the ductwork specified as “unsealed ducts” by ASHRAE. On the other hand, thermal losses from supply ducts induced by conduction (including convection and radiation) were significant, on the scale that was comparable to the losses induced by air leakage in the duct systems. The energy losses induced by leakage and conduction suggested that there exist significant energy savings potentials from duct sealing and duct insulation practice in large commercial buildings. |
Databáze: | OpenAIRE |
Externí odkaz: |