The impact of grid negative sequence voltage to STATCOM and control
Autor: | Renjie Hu, Guiping Yi |
---|---|
Rok vydání: | 2013 |
Předmět: |
Engineering
business.industry Voltage divider Hardware_PERFORMANCEANDRELIABILITY Voltage regulator Voltage optimisation Condensed Matter::Mesoscopic Systems and Quantum Hall Effect Disturbance voltage Dropout voltage Control theory Hardware_INTEGRATEDCIRCUITS Voltage droop Voltage regulation business Negative impedance converter |
Zdroj: | 2013 International Conference on Electrical Machines and Systems (ICEMS). |
DOI: | 10.1109/icems.2013.6713344 |
Popis: | Industrial Static Synchronous Compensator (STATCOM) is typically applied at or near the load center to mitigate voltage fluctuation, flicker, phase unbalance, non-sine distortion or other load-related disturbance. Special attention is paid to the influence of grid negative sequence voltage to STATCOM current, the unbalance of grid voltage causes not only the AC current unbalance but also the DC voltage fluctuation. In order to let the inverter voltage contain the fundamental negative sequence component corresponding to the grid voltage, a new dual-loop control scheme is proposed to suppress the influence in this paper. The negative sequence voltage decomposition algorithm is also introduced. The validity of all analyses is verified by the simulation. |
Databáze: | OpenAIRE |
Externí odkaz: |