Enhancing performance of wall mounted split air conditioner using capillary tube in a tube heat exchanger
Autor: | Amay Suherman, M Mutaufiq, E T Berman, Mumu Komaro, M Miftakhudin |
---|---|
Rok vydání: | 2020 |
Předmět: | |
Zdroj: | IOP Conference Series: Materials Science and Engineering. 830:042033 |
ISSN: | 1757-899X 1757-8981 |
DOI: | 10.1088/1757-899x/830/4/042033 |
Popis: | The high cost of electricity rates has affected the demands of the public for the availability of energy-efficient air conditioning systems. This study aims to obtain data on improving performance of air conditioner using capillary tube in tube heat exchangers. Tests were carried out on a wall mounted split AC capacity of 9000 Btu/h which was modified using a heat exchanger with capillary tube in tube heat exchanger. The results showed that the installation of a capillary tube in tube heat exchanger on a wall mounted split AC resulted in an increase RE and COP of 13.2% and 14.9%, respectively. In addition, the room cooling time in the TiTHX capillary mode testing is shorter. So it has implications for lighter compression work and saves the power consumption required by AC. |
Databáze: | OpenAIRE |