Thermal Comfort Study of Wall Hanging Air-Conditioning Office in Summer

Autor: Xu Sheng Chai, Zhi Qiu Fu, Lan Xia Guo, Jian Xiang Liu, Jing Jing Liang, Xiao Yong Peng
Rok vydání: 2014
Předmět:
Zdroj: Advanced Materials Research. :1088-1091
ISSN: 1662-8985
DOI: 10.4028/www.scientific.net/amr.1008-1009.1088
Popis: Airpak was applied to numerically simulate the air distribution under the same air supply temperature ,different air supply velocity (3.6m/s、2.7m/s and 1.8m/s ) and air supply angle (+15°、-45° and-75°) , and evaluate thermal comfort by Comparative analysis velocity fields, temperature fields, PMV—PPD. The results show that different air supply velocity and air supply angle have a significant impact on indoor air distribution under the same air supply temperature. Air supply angle Plays a vital role in pattern and distribution of indoor flow field,air supply velocity mainly effect the magnitude of indoor velocity and temperature. Synthetically comparied, the model’s best supply parameters are supply velocity 2.7m/s and supply angle75°,which mean value of indoor PMV is-0.09, PPD is 8.5%.
Databáze: OpenAIRE