Research on High-voltage Switch Cabinet's Multi-channel Power-on Comprehensive Diagnostic Technology
Autor: | Aoran Xu, Jinming Luo, Yixuan Gao, Jing Gao, Yuxiu Zang |
---|---|
Rok vydání: | 2018 |
Předmět: |
business.industry
Computer science 020208 electrical & electronic engineering Electrical engineering 020206 networking & telecommunications High voltage 02 engineering and technology Switchgear Experimental research Pulse waveform Partial discharge Diagnostic technology 0202 electrical engineering electronic engineering information engineering business Multi channel Pulse wave form |
Zdroj: | 2018 China International Conference on Electricity Distribution (CICED). |
DOI: | 10.1109/ciced.2018.8592583 |
Popis: | In this paper, the author summarizes four discharge patterns based on the analysis of common high-voltage switch cabinet faults and the causes of insulation faults with highest fault rate. By establishing the high-voltage switch cabinet's multichannel power-on comprehensive diagnostic platform, the author uses the needle plate discharge model to simulate partial discharge source so as to conduct the experimental research and uses four-channel transmission signals' arrival sequence to conduct the partial discharge source positioning. Based on the comparative analysis of partial discharge signals through simulation, the author adopts the anti-jamming technology to conduct the research on internal discharge and external interference signals' pulse wave form. Based on the discharge signals' pulse waveform, the author successfully establishes high-voltage switch cabinet's anti-jamming partial discharge detection system. |
Databáze: | OpenAIRE |
Externí odkaz: |