Bottom-up evidence-based calibration of the HVAC air-side loop of a building energy model
Autor: | Andreea Mihai, Radu Zmeureanu |
---|---|
Rok vydání: | 2016 |
Předmět: |
Engineering
business.industry 020209 energy Cooling load Building model 02 engineering and technology Building and Construction Computer Science Applications law.invention Air conditioning law Modeling and Simulation Architecture Thermal HVAC Ventilation (architecture) 0202 electrical engineering electronic engineering information engineering Calibration business Simulation Marine engineering Building automation |
Zdroj: | Journal of Building Performance Simulation. 10:105-123 |
ISSN: | 1940-1507 1940-1493 |
DOI: | 10.1080/19401493.2016.1152302 |
Popis: | This paper proposes an evidence-based bottom-up method to calibrate the heating, ventilation, and air conditioning air-side loop of a building energy model. The building model is calibrated using Building Automation System trend data for each thermal zone with respect to the supply air flow rate, indoor air temperature, and cooling load. The calibration at the air-handling unit (AHU) level is based on the supply air flow rate leaving the AHU, and the cooling coil load. The calibration quality is evaluated by using graphical representation, statistical indices, and paired hypothesis testing. The results proved that once the calibration of supply air flow rate was achieved for most zones, the AHU model was calibrated with respect to supply air flow rate and cooling coil load, without any additional tuning through the trial-and-error method. |