Study on the Analysis of Differential Pressure of the Access Door for a Smoke Control Zone and the Effectiveness of the Measurement Criteria of its Opening Force

Autor: Chung-Seog Choi, Jae-Ou Lee
Rok vydání: 2012
Předmět:
Zdroj: Journal of Korean Institute of Fire Science and Engineering. 26:24-30
ISSN: 1738-7167
DOI: 10.7731/kifse.2012.26.4.024
Popis: The purpose of this study is to analyze the problem in measuring the differential pressure between the fire area and the neighboring smoke control zone as well as the opening force of a fire door and to present the actual values measured by an objective method. NFSC 501A specifies that the force necessary to open an access door when operating a smoke control system shall be less than 110 N. When the smoke control system does not operate in the space where it is installed, the door opening force can be measured by the test method in KS F 2805. However, when the smoke control system operates, additional opening force is required to overcome the force generated by the differential pressure between the fire area and smoke control room. Therefore, it can be seen that the method proposed by the standard has insufficient reliability. The analog measuring device and digital measuring device showed that the opening forces, and , of the fully closed door before the smoke control system were 27.8 N and 27.4 N, respectively. When the door remained open by , the opening forces, and , were 33 N and 33.6 N, respectively. When the smoke control system operated and the door was fully closed, the door opening forces, and , were 77.6 N and 76.0 N, respectively. Therefore, since the door opening forces are different from the criteria presented by KS F 2805, it is required to review the criteria appropriately.
Databáze: OpenAIRE