Autor: |
Singh, Nitesh, Permana, Indra, Agharid, Alya Penta, Wang, Fu-Jen |
Zdroj: |
Thermal Science and Engineering Progress; January 2025, Vol. 57 Issue: 1 |
Abstrakt: |
•Field measurements of a data center were conducted before and after retrofitting.•Recirculation and overheating werereduced by 69% with a drop in the β index.•SHI, RHI, and RTI values improved by 71.1%, 77%, and 11.9% after retrofitting.•Temperature distribution became more uniform, eliminating hot spots.•Cooling performance optimized with reduced energy consumption. |