Autor: |
Lock, G. S. H., Simpson, G. A. |
Zdroj: |
Journal of Offshore Mechanics and Arctic Engineering; February 1989, Vol. 111 Issue: 1 p22-28, 7p |
Abstrakt: |
The experimental work reported here is concerned with the single-phase closed thermosyphon under conditions which are appropriate to a northern application: large length-diameter ratios and heated lengths much greater than cooled lengths. The purpose is twofold: to generate empirical heat transfer data which represent the conservative lower limit of performance (in the absence of boiling or bubbling); and to reveal the thermal and momentum exchange mechanisms which operate at the junction of the heated and cooled sections. The apparatus consisted of a 102-mm-dia, vertical steel pipe of overall length varying from 2 m to 6 m. The lower section of the pipe was heated by means of electric-resistive tape, and the upper section cooled by means of a water jacket. Heat transfer data, plotted in the usual form of Nusselt number versus the quotient of the Rayleigh number and the length-diameter ratio, show the effect of geometry. This data was obtained for 10 ≤ LH/d ≤ 50, and 1 ≤ LH/Lc ≤ 20. An empirical correlation is developed. |
Databáze: |
Supplemental Index |