Determining the performance of a commercial air purification system for reducing airborne contamination using model micro-organisms: a new test methodology.

Autor: Griffiths, W.D., Bennett, A., Speight, S., Parks, S.
Zdroj: Journal of Hospital Infection; Nov2005, Vol. 61 Issue 3, p242-247, 6p
Abstrakt: Summary: The performance of a duct-mounted air disinfection system, designed to reduce airborne pathogens in the hospital environment, was determined using a new testing methodology. The methodology places the equipment in a test duct, a microbial aerosol is generated and then sampled simultaneously before and after the test system. This allows a percentage efficiency value to be calculated. The air disinfection system is a novel chemical-coated filter and ultraviolet (UV) radiation air purification system, operating at a flow rate of 500m3/h, against aerosols of MS2 phage and Mycobacterium vaccae (surrogates of viral and mycobactericidal pathogens). A three UV lamp system was effective against airborne phages, removing an average of 97.34% of the aerosolized challenge. With the UV component switched off, the average efficiency dropped to 61.46%. This demonstrates that the chemical-coated filter component plays a more significant role than the UV radiation in destroying phages. When six UV lamps were used, the system was able to remove mycobacteria with an efficiency exceeding 99.99%. This test methodology can be used to assess manufacturers'' claims of efficacy of equipment against airborne micro-organisms in the hospital environment. [Copyright &y& Elsevier]