Abstrakt: |
The effects of cooling methods, gas pressure, gas velocity, electrical loading, and environmental parameters on the steady-state temperature distribution of SF6 gas-cooled-insulated power transformers are investigated by using the finite-element method. The contributions of convection and radiation to the total heat-transfer rate inside and outside the transformer are included. The results provide useful sensitivity information which can be accessed and manipulated by the transformer designers or operators. This sensitivity information significantly reduces the analysis and computations via identifying the important parameters that most affect the temperature distribution in this type of transformer. [ABSTRACT FROM AUTHOR] |