Autor: |
HS, Arunkumar, N, Madhwesh, Shenoy, Shankar, Kumar, Shiva |
Zdroj: |
International Journal of Sustainable Engineering; Dec2024, Vol. 17 Issue 1, p469-480, 12p |
Abstrakt: |
To overcome the drawbacks of a single-stage evaporative cooler, an indirect-direct type evaporative cooler was proposed and fabricated. An alternative arrangement of mild steel plates wherein unmixed heat transfer occurs between air and water to form an indirect evaporative cooler. This is followed by a packing arrangement made of biomass-based coconut coir that forms a direct evaporative cooler. Experiments were conducted by varying the air and water flow rates, and the performance of the coconut coir was compared with that of a commercially available celdek packing. Experimental results indicated that a combination of an indirect-direct evaporative cooler helped cool air without an appreciable increase in air-specific humidity. The performance of the coconut coir is slightly lower than that of the Celdek coir in terms of the drop in DBT and wet-bulb effectiveness. A maximum wet bulb effectiveness of 0.78 and 0.63 was achieved for the celdek and coconut coir packings, respectively. The maximum performance was attained at an air velocity of 6 m/s and a water flow rate of 3 LPM. Owing to the different advantages of coconut coir over celdek packings, it is recommended to use coconut coir as an alternative packing in indirect-direct evaporative coolers. [ABSTRACT FROM AUTHOR] |
Databáze: |
Complementary Index |
Externí odkaz: |
|