Abstrakt: |
Active power filters (APFs) play a vital role in reducing the current harmonics and improving power quality. This work studies a shunt APF (SAPF) based on the threephase voltage source converter (VSC). This paper investigates the new robust control approach using error dynamics. Stable first-order error dynamics are considered when designing the control inputs. Three control inputs are obtained to control the currents at any phase by choosing and optimizing the appropriate parameters. This strategy is also simple to implement in practical applications because it is the same as the proportionalderivative controller design. In addition, the new control method can be utilized for any system with low dynamic information so that the destructive effects of lumped uncertainties in the output channels of the SAPF can be alleviated. The minimum voltage and current measurements are used to control the SAPF, and the grid current harmonics will be reduced by achieving the stabilization of tracking error dynamics. Some numerical simulations are performed by MATLAB software to confirm the proposed method. [ABSTRACT FROM AUTHOR] |