Abstrakt: |
The active and reactive load changes have a significant impact on voltage and frequency. In this paper, in order to stabilize the microgrid (MG) against load variations in islanding mode, the active and reactive power of all distributed generators (DGs), including energy storage (battery), diesel generator, and micro-turbine, are controlled. The micro-turbine generator is connected to MG through a three-phase to three-phase matrix converter, and the droop control method is applied for controlling the voltage and frequency of MG. In addition, a method is introduced for voltage and frequency control of micro-turbines in the transition state from gridconnected mode to islanding mode. A novel switching strategy of the matrix converter is used for converting the high-frequency output voltage of the micro-turbine to the grid-side frequency of the utility system. Moreover, using the switching strategy, the low-order harmonics in the output current and voltage are not produced, and consequently, the size of the output filter would be reduced. In fact, the suggested control strategy is load-independent and has no frequency conversion restrictions. The proposed approach for voltage and frequency regulation demonstrates exceptional performance and favorable response across various load alteration scenarios. The suggested strategy is examined in several scenarios in the MG test systems, and the simulation results are addressed. [ABSTRACT FROM AUTHOR] |