INFLUENCE OF COMPRESSOR SPEED ON THE PERFORMANCE OF LOW PRESSURE VAPOR-INJECTED REFRIGERATION SYSTEMS.

Autor: Haijun LI, ZhiYong SU, ChaoYue ZHAO, Tong AN, XingDuo QIN, Gang CHEN, JiaYang GAO, YiBo ZHANG
Předmět:
Zdroj: Thermal Science; 2024, Vol. 28 Issue 3A, p2043-2049, 7p
Abstrakt: For the problems of high compressor discharge temperature and system performance decay during the operation of cold storage, a parallel flow heat exchanger based low pressure make-up gas refrigeration system experimental bench was designed and built, and the changes of refrigeration system performance were analyzed under different compressor speeds. The results show that when the compressor speed increases from 2500 rpm to 4500 rpm, the compressor discharge temperature increases, the refrigeration capacity increases by 39.53% and the compressor power increases by 38.89%, in addition, as the speed increases, the system COP shows a trend of first increasing and then decreasing, with the best value of 2.71 at 3500 rpm. [ABSTRACT FROM AUTHOR]