Fluids; Jan2023, Vol. 8 Issue 1, p14, 16p |
Abstrakt: |
In this work, four radiators with different core geometries were tested using a wind tunnel. The values of the global heat transfer coefficient (UA = 5 ÷ 65 W/K) were measured depending on the flow of air and water. The obtained UA values correlate well with the data of sorption experiments described in the literature. The found correlations between the Nusselt and Reynolds numbers made it possible to propose an algorithm for ranging commercial air radiators for the use in adsorption heat transformers. It is shown that the use of a wind tunnel can serve as an effective tool for express assessment of the prospects of using air radiators for adsorption heat conversion without destroying radiators or their direct testing in a complex adsorption installation requiring vacuum maintenance. [ABSTRACT FROM AUTHOR] |