Autor: |
Cai, Dongxiao, Li, Haifeng, Zhu, Xinchi |
Předmět: |
|
Zdroj: |
Journal of Engineering; Apr2019, Vol. 2019 Issue 4, p1275-1279, 5p |
Abstrakt: |
Here, the response characteristics of high-voltage DC (HVDC) control system are studied in the case that fault occurs in the sending-end AC system. Then the characteristics of DC system which is equivalent to power-frequency variation impedance in the fault super-imposed network are analysed by mathematical derivation and verified by simulations on PSCAD/EMTDC. The result shows that the equivalent power-frequency variation impedance of HVDC system is affected by the rated capacity and the parameters of HVDC control system. The power-frequency variation impedance becomes capacitive under certain fault conditions, which reduces the zone of distance protection based on power-frequency variation and even leads to the operation failure. [ABSTRACT FROM AUTHOR] |
Databáze: |
Complementary Index |