Autor: |
Ku, Te-Tien, Lin, Chia-Hung, Hsu, Cheng-Ting, Chen, Chao-Shun, Liao, Zhan-Yi, Wang, Shuo-De, Chen, Fung-Fei |
Předmět: |
|
Zdroj: |
IEEE Transactions on Industry Applications; Nov/Dec2020, Vol. 56 Issue 6, p6150-6157, 8p |
Abstrakt: |
This article presents the innovative control scheme of renewable ancillary services to support the system operation of a bulk power system with high penetration of renewable energy. The smart inverters of PV systems can be controlled to adjust the renewable generation of real and reactive power according to the variation of system voltage and frequency. The dispatch control of renewable ancillary services is integrated with the energy management system to achieve the coordination control of renewable energy and synchronous generators. The sensitivity factors of renewable system was applied to determine the generation curtailment for the mitigation of line overloading. The ancillary service of reactive power compensation by renewable energy was considered to improve the system voltage quality. The emergency generation control of renewable systems with fast ramping up capability was applied to illustrate the effectiveness of renewable ancillary service to improve the system frequency response after sudden generator tripping. Based on the computer simulation of an actual power system with large renewable energy to be integrated, the functions of virtual synchronous generators by the photovoltaic systems and wind farms have to be applied to ensure the successful steady-state operation and to improve the system transient stability for severe disturbance contingency. [ABSTRACT FROM AUTHOR] |
Databáze: |
Complementary Index |
Externí odkaz: |
|