Condition assessment of naturally aged composite insulators, aiming to better understand the ageing processes involved, is essential for maintaining high reliability in power networks. In this study field-ageing effects on insulating materials (EPDM and VMQ/HCR) of two 150 kV composite suspension insulators are evaluated. The insulators had been in service for 17 years on a coastal transmission network, exposed to seaborne salt spray, windborne soil deposits and intense UV solar radiation. Several diagnostic techniques, including visual inspection, wettability classification, FTIR spectroscopy, SEM and EDX analysis were employed to assess the condition of the insulators. Field-ageing effects were not assessed as critical to dictate insulator replacement. For both insulators morphological and material degradation due to field-ageing was restricted to the upper surface layer of the polymeric housing. The resistance of housing material against tracking and erosion remained unaffected by field-ageing. Surface deterioration of EPDM was more intense than that of VMQ/HCR, despite the fact that the EPDM insulator had been in operation at a site with a lower pollution severity. The EPDM housing was classified as hydrophilic; however, after removing pollutant deposits its hydrophobicity was improved. The hydrophobic properties of the VMQ/HCR housing were only slightly reduced. Field-ageing effects on insulator housing are discussed based on material structural changes caused by ageing stresses. [ABSTRACT FROM AUTHOR] |
Databáze: |
Complementary Index |
Externí odkaz: |
|