Influence of acidification of circulating water on differential distribution of dispersed phase.

Autor: Gulyaenko, O. B., Chichenin, V. V., Ahrameev, V. G.
Zdroj: Proceedings of Odessa Polytechnic University / Odes'kyi Politechnichnyi Universytet Pratsi; 2015, Vol. 46 Issue 2, p75-78, 4p
Abstrakt: The paper analyzes the connection between processing technologies of circulating water cooling tower and coagulation-aggregation properties of colloidal particles of the dispersed phase. In circulating water cooling tower when clarifying additional water the reduction of HCO3- and CO32- concentrations happens with corresponding pH increase. Absorption of atmospheric carbon dioxide by cooling tower circulating water offsets this increase. The estimation of the probability of adhesion to the surface of the dispersed phase, distributed in the volume of circulation water, and the heat exchange surface of the condenser for different degrees of evaporation of the coolant is made. The distribution of cooling water micro-disperse particles which are adsorbed on the heat exchange surfaces of the condenser (deposit formation) and on the surface of larger particles (particle aggregation) reflects the efficiency of applied water treatment technology. It is shown that acidification of additional water facilitates solution of most fine fractions and increases hardness of treated water. [ABSTRACT FROM AUTHOR]