Online Condition Assessment of Interruption Chamber of Gas Circuit Breakers Using Arc Voltage Measurement
Autor: | Kaveh Niayesh, Asghar Bagherpoor, Ali Asghar Razi-Kazemi, Sadegh Rahimi-Pordanjani |
---|---|
Rok vydání: | 2017 |
Předmět: |
Engineering
Transient recovery voltage business.industry 020209 energy Electrical engineering Energy Engineering and Power Technology 02 engineering and technology Power (physics) Arc voltage Electric power system Pre-charge 0202 electrical engineering electronic engineering information engineering Key (cryptography) Electrical and Electronic Engineering Current (fluid) business Circuit breaker |
Zdroj: | IEEE Transactions on Power Delivery. 32:1776-1783 |
ISSN: | 1937-4208 0885-8977 |
DOI: | 10.1109/tpwrd.2016.2597302 |
Popis: | As a key element of a power system, a circuit breaker (CB) requires regular maintenance. Intelligent online condition assessment is increasingly becoming a requirement for key items of power plants, including CBs. The interruption chamber, as the most critical part of the CBs, plays an important role in the proper operation of CBs. Online assessment of this part is difficult from a technical perspective due to the high noise level and presence of a transient recovery voltage. This paper proposes a set up for the online measurement of the CB arc voltage during trip/close operations. In addition, a method has been proposed to evaluate the remaining useful lifetime of the interruption chamber based on the measured arc voltage and current. The setup and the proposed approach are verified experimentally. |
Databáze: | OpenAIRE |
Externí odkaz: |