Direct method for transient stability assessment of a single wind turbine generator subject to LVRT requirements
Autor: | Adriano Lima Abrantes, Luis F. C. Alberto, Alexandre Prodóssimo Sohn |
---|---|
Rok vydání: | 2020 |
Předmět: |
Wind power
Dynamical systems theory business.industry Computer science Rotor (electric) 020209 energy 020208 electrical & electronic engineering Energy Engineering and Power Technology 02 engineering and technology Turbine law.invention Acceleration Electric power system Control and Systems Engineering Control theory Steam turbine law 0202 electrical engineering electronic engineering information engineering Transient (oscillation) Electrical and Electronic Engineering business |
Zdroj: | IET Generation, Transmission & Distribution. 14:6195-6205 |
ISSN: | 1751-8695 1751-8687 |
DOI: | 10.1049/iet-gtd.2020.1313 |
Popis: | The authors report on a step towards the development of direct methods for transient stability assessment of power systems with integrated wind turbine generators subject to low voltage ride-through constraints. In this study, they propose an approach to assess transient stability of a single wind turbine generator against an infinite bus using an energy function along with an extension of the potential energy boundary surface method. The proposed approach exploits the theory of constrained dynamical systems and the concept of constrained stability region to efficiently estimate critical clearing times taking into account not only the issue of stability due to rotor acceleration but also the issue of operational limit violations, such as low-voltage ride-through curve violations. Very often, wind turbine generators are disconnected due to violation of operational limits, such as under-voltage limits, instead of rotor acceleration. The proposed approach correctly estimates the critical clearing times to avoid operational limit violations, such as the low-voltage ride-through constraint violation, while traditional direct methods would fail to appropriately estimate such clearing times. They illustrate the effectiveness of the proposed approach by means of case studies considering two types of wind turbine generators, the fixed- and limited-variable-speed wind turbine generators. |
Databáze: | OpenAIRE |
Externí odkaz: |