Development of 20 integrated energy efficiency ratio rooftop units—system modeling and building energy simulations
Autor: | Wendy Liu, Keith Rice, Edward Allan Vineyard, Bo Shen |
---|---|
Rok vydání: | 2013 |
Předmět: | |
Zdroj: | HVAC&R Research. 19:836-846 |
ISSN: | 1938-5587 1078-9669 |
DOI: | 10.1080/10789669.2013.826064 |
Popis: | Based on a detailed steady-state system and component modeling, a rooftop unit system design was developed that is can achieve an integrated energy efficiency rating higher than 20. Fin-and-tube and microchannel heat exchangers were modeled using a segment-to-segment approach, and an AHRI 10-coefficient compressor map used to simulate compressor performance. The system modeling is based on a component-based modeling approach, which facilitates flexible simulation of complicated system configurations. Starting with a baseline system having integrated energy efficiency rating of 16.6, numerous technical options were extensively investigated, i.e., varying compressor sizes, heat exchanger fin densities, fin-and-tube or microchannel heat exchanger, suction line heat exchanger, desiccant wheel, tandem compressor (TD), variable-speed compressor (VS), and condenser evaporative pre-cooling; an innovative system configuration was developed by combining a tandem compression system with a variable-speed compression ... |
Databáze: | OpenAIRE |
Externí odkaz: | |