Large-scale fire suppression modeling of corrugated cardboard boxes on wood pallets in rack-storage configurations
Autor: | Ning Ren, Karl V. Meredith, Xiangyang Zhou, Yi Wang, Jaap de Vries, Marcos Chaos |
---|---|
Rok vydání: | 2017 |
Předmět: |
Convection
Engineering Water transport business.industry Corrugated fiberboard 0211 other engineering and technologies General Physics and Astronomy 020101 civil engineering 02 engineering and technology General Chemistry Mechanics Solid fuel 0201 civil engineering Rack Flame spread 021105 building & construction Fire protection General Materials Science Pallet Safety Risk Reliability and Quality business Simulation |
Zdroj: | Fire Safety Journal. 91:695-704 |
ISSN: | 0379-7112 |
DOI: | 10.1016/j.firesaf.2017.04.008 |
Popis: | In this study, the fire growth and suppression models in FireFOAM were validated for rack-storage commodities consisting of two solid fuels, namely corrugated cardboard boxes and hardwood pallets, which are referred to as Class 2 commodity. Validation experiments included two fire-growth and two fire-suppression configurations with different rack-storage array heights (3 and 5 tiers). In the suppression study, standard-response upright ceiling sprinklers (K-factor of 160 lpm/bar1/2) were used. The time-resolved chemical heat release rates obtained from the experiments were used to validate the fire growth model. The observed sprinkler activations and fire-spread patterns were used to validate the suppression model. This study identified that lateral flame spread is primarily enabled by flames impinging on the commodity's bottom surfaces. This study also showed that obstructions, such as wood pallets, can significantly impede convective and radiative heat transfer to the underside of the commodity, reducing the lateral flame spread rate. Fire-suppression modeling revealed that both surface water transport and lateral flame spread rates are important when predicting fire-suppression behavior. Therefore, as the rack-storage array height increases, so does the water transport time, which results in the fire becoming more difficult to control. Likewise, as the lateral spread rate increases, e.g., as occurs in the absence of wood pallets, fire-suppression also becomes more difficult. |
Databáze: | OpenAIRE |
Externí odkaz: |