DESIGN OF A BUILDING FIRE PUMP SYSTEM WITH INTEGRATED PARALLEL PUMP
Autor: | Kimar Turnip, Rahmad Samosir, Leonard Michael Odi Nathanael |
---|---|
Rok vydání: | 2021 |
Předmět: |
Pressure drop
Fire extinguisher Computer science ComputingMilieux_PERSONALCOMPUTING Hardware_PERFORMANCEANDRELIABILITY Signal Automotive engineering law.invention TheoryofComputation_MATHEMATICALLOGICANDFORMALLANGUAGES law Backup Hardware_INTEGRATEDCIRCUITS Pressure switch Fire pump ComputerSystemsOrganization_SPECIAL-PURPOSEANDAPPLICATION-BASEDSYSTEMS Governor |
Zdroj: | International Journal of Research -GRANTHAALAYAH. 9:203-215 |
ISSN: | 2350-0530 2394-3629 |
DOI: | 10.29121/granthaalayah.v9.i2.2021.3374 |
Popis: | Multi-storey building must be equipped with a reliable building fire extinguishing system. The existing fire extinguishing system design is not equipped with a backup pump and a jockey pump. Based on The DKI Jakarta Governor Regulation No. 92/2014 and the Indonesian National Standard, to solve this problem, a building fire pump system is designed with a combination of the jockey pump, main pump and backup pump that connected in an integrated parallel arrangement. This design allows the backup pump to automatically run due to a pressure drop in the system pipe if the main pump fails or unable to build up pressure. When a fire occurs and a lot of hydrants are used, the backup pump will automatically run to help the main pump with a signal triggered by the pressure switch. |
Databáze: | OpenAIRE |
Externí odkaz: |