Autor: |
D Rochette, S Clain, P Andre, W Bussiere, F Gentils |
Předmět: |
|
Zdroj: |
Journal of Physics D: Applied Physics; May2007, Vol. 40 Issue 10, p3137-3144, 8p |
Abstrakt: |
Medium voltage (MV) cells have to respect standards (for example IEC ones (IEC TC 17C 2003 IEC 62271-200 High Voltage Switchgear and Controlgear--Part 200 1st edn)) that define security levels against internal arc faults such as an accidental electrical arc occurring in the apparatus. New protection filters based on porous materials are developed to provide better energy absorption properties and a higher protection level for people. To study the filter behaviour during a major electrical accident, a two-dimensional model is proposed. The main point is the use of a dedicated numerical scheme for a non-conservative hyperbolic problem. We present a numerical simulation of the process during the first 0.2 s when the safety valve bursts and we compare the numerical results with tests carried out in a high power test laboratory on real electrical apparatus. [ABSTRACT FROM AUTHOR] |
Databáze: |
Complementary Index |
Externí odkaz: |
|