Bandwidth oriented approach for the design of a PI controller for a three phase two-stage grid-connected PV system.

Autor: Murdan, Anshu Prakash, Jahmeerbacus, Iqbal, Sayed Hassen, S Z
Předmět:
Zdroj: International Journal of Electronics; Jun2024, Vol. 111 Issue 6, p1033-1053, 21p
Abstrakt: The two-stage power converter is currently the most widespread topology for three-phase grid-connected photovoltaic (PV) systems. The PV power is injected to the grid through the regulation of the dc-link voltage. This method is commonly called the voltage control method, whereby the current is controlled indirectly. This paper focuses on the modelling of power converters and the parameter design of proportional-integral (PI) controllers, based on the bandwidth of the inner current loop and the outer voltage loop. It is assumed that the inner loop has a bandwidth that is ten-fold bigger than that of the outer loop, in order to fully decouple the dual loops. The PI parameters are thus determined through this relationship, and two sets of simulations are run to validate the methodology used. Results show that the controllers give highly satisfactory performance even in the presence of transients introduced by rapidly varying irradiance model. [ABSTRACT FROM AUTHOR]
Databáze: Complementary Index