Autor: |
Guest, Emerson, Jensen, Kim H., Rasmussen, Tonny W. |
Zdroj: |
IEEE Transactions on Sustainable Energy; Apr2020, Vol. 11 Issue 2, p785-794, 10p |
Abstrakt: |
In this paper, active filters are embedded in the grid-connected converter control of Type-IV wind turbines to reduce harmonic voltage amplification in offshore wind power plants (WPPs). The extra element theorem is employed to tune the active filters and determine the stability margin. Active filter tunings that satisfactorily reduce harmonic voltage amplification yet provide sufficient stability margin in the augmented system are identified. A running example is performed on a 270 MW offshore WPP comprised of 3-MW wind turbines implemented in real-time simulation as hardware-in-the-loop. Both converter and grid voltage harmonics are suppressed at WPP buses to below the stipulated planning levels. [ABSTRACT FROM AUTHOR] |
Databáze: |
Complementary Index |
Externí odkaz: |
|